RIGID CONDUIT AND KNOCKOUT SIZES
ALL SIZES ARE INCHES |
INSIDE DIAMETER |
OUTSIDE DIAMETER |
KNOCKOUT SIZE |
||
TRADE |
THREADS |
NOMINAL |
NOMINAL |
MAXIMUM |
NOMINAL |
1/4 |
18 |
.364 |
.540 |
- |
.575 |
3/8 |
18 |
.493 |
.675 |
- |
.718 |
1/2 |
14 |
.632 |
.840 |
.855 |
.875 |
3/4 |
14 |
.836 |
1.050 |
1.066 |
1.109 |
1 |
11-1/2 |
1.063 |
1.315 |
1.331 |
1.375 |
1-1/4 |
11-1/2 |
1.394 |
1.660 |
1.676 |
1.734 |
1-1/2 |
11-1/2 |
1.624 |
1.900 |
1.916 |
1.984 |
2 |
11-1/2 |
2.083 |
2.375 |
2.399 |
2.469 |
2-1/2 |
8 |
2.489 |
2.875 |
2.904 |
2.969 |
3 |
8 |
3.090 |
3.500 |
3.535 |
3.594 |
3-1/2 |
8 |
3.570 |
4.000 |
4.040 |
4.123 |
4 |
8 |
4.050 |
4.500 |
4.545 |
4.641 |
4-1/2 |
8 |
4.506 |
5.000 |
5.050 |
5.109 |
5 |
8 |
5.073 |
5.563 |
5.619 |
5.719 |
6 |
8 |
6.093 |
6.625 |
6.691 |
6.813 |
| (1) | U.L. Table NAE.3. |
| (2) | Maximum Outside Diameter Per ANSI C80.1-1977. |
| (3) | Dimensions for trade sizes of 1/4 through 1-1/4 are from
Table 20.2 of ANSI/UL 514-1978. Sizes 1/ 2 " thru 6" per proposed revision to NEMA Engineering Bulletin No. 71, Aug. 1976. |
PLASTIC CONDUIT BUSHING SIZES
ALL SIZES ARE INCHES |
TRADE |
DIMENSION |
DIMENSION |
|
1/2 |
1.050 |
.365 |
3/4 |
1.280 |
.390 |
|
1 |
1.632 |
.490 |
|
1-1/4 |
1.986 |
.535 |
|
1-1/2 |
2.160 |
.550 |
|
2 |
2.680 |
.600 |
|
2-1/2 |
3.150 |
.635 |
|
3 |
3.800 |
.725 |
|
3-1/2 |
4.275 |
.725 |
|
4 |
4.775 |
.750 |
|
5 |
6.350 |
.975 |
|
6 |
7.475 |
.975 |
INTERMEDIATE METALLIC CONDUIT (IMC)
ALL SIZES ARE INCHES |
INSIDE DIAMETER |
OUTSIDE DIAMETER |
||
TRADE |
THREADS |
NOMINAL |
NOMINAL |
MAXIMUM |
1/2 |
14 |
.675 |
.815 |
.820 |
3/4 |
14 |
.879 |
1.029 |
1.034 |
1 |
11-1/2 |
1.120 |
1.290 |
1.295 |
1-1/4 |
11-1/2 |
1.468 |
1.638 |
1.645 |
1-1/2 |
11-1/2 |
1.703 |
1.883 |
1.890 |
2 |
11-1/2 |
2.170 |
2.360 |
2.367 |
2-1/2 |
8 |
2.597 |
2.857 |
2.867 |
3 |
8 |
3.216 |
3.476 |
3.486 |
3-1/2 |
8 |
3.711 |
3.971 |
3.981 |
4 |
8 |
4.206 |
4.466 |
4.476 |
| U.L. Proposed Dimensions for Intermediate Metallic Conduit - Type I. | |
| IMC Threads and Knockout Sizes are the same as Rigid Metal Conduit. | |
| Standard rigid threaded conduit fittings can be used with I.M.C. |
ELECTRICAL METALLIC TUBING (EMT)
ALL SIZES ARE INCHES |
INSIDE DIAMETER |
WALL |
OUTSIDE DIAMETER |
|
TRADE |
NOMINAL |
NOMINAL |
NOMINAL |
TOLERANCE |
3/8 |
.493 |
.042 |
.577 |
+/- .005 |
1/2 |
.622 |
.042 |
.706 |
+/-.005 |
3/4 |
.824 |
.049 |
.922 |
+/-.005 |
1 |
1.049 |
.057 |
1.163 |
+/-.005 |
1-1/4 |
1.380 |
.065 |
1.510 |
+/-.005 |
1-1/2 |
1.610 |
.065 |
1.740 |
+/-.005 |
2 |
2.067 |
.065 |
2.197 |
+/-.005 |
* 2-1/2 |
2.731 |
.072 |
* 2.875 |
+/-.010 |
* 3 |
3.356 |
.072 |
* 3.500 |
+/-.015 |
* 3-1/2 |
3.834 |
.083 |
* 4.000 |
+/-.020 |
* 4 |
4.334 |
.083 |
* 4.500 |
+/-.020 |
| * | These sizes of EMT have the same nominal outside diameter as the corresponding size rigid conduit. |
| EMT is sometimes called "thin-wall conduit". | |
E-Mail me. and